Quick Brief

Place of Origin: Maharashtra IndiaBrand Name: MEGATECHModel Number: MPS 20
Phase: Three Phase To Three PhaseProtection: Short CircuitWeight: 200 KGs
Output Voltage: 230V AC Single PhaseType: On-lineApplication: Computer

Product Features:

1) High Quality Maxima UPS System

2) Reasonalbe price

3) On Time delivery

Product Cateogry: Uninterrupted Power Supply (UPS)

Business Term:

Port: MUMBAI JNPT

Minimum Order Quantity: 10 Piece/Pieces As per buyers requirement

Supply Ability: As per buyers requirement

Payment Terms: L/C,T/T

 
Contact Supplier
MAXIMA UPS SYSTEM

Packaging Information

Packaging Detail:Export Worthy Packaging
Delivery Detail:AS PER CUSTOMER REQUIREMENT

Specifications and Product Details:

Original Product Page

Maxima UPS System

TECHNICAL SPECIFICATIONS FOR ONLINE UPS 3Ph to 3Ph Maxima Series MPS 60
ModelMPS 60
Rating60 KVA
AC INPUT415V + 15% -20% Three Phase Input
Frequency50Hz ± 6%
DC VOLTAGE:360VDC
Charging Time12 Hours for 90% of full Capacity
Charger TypeCVCC Internal Controlled Rectifier type

INVERTER:

TechnologyIGBT Double Conversion
Output Voltage400V AC Three Phase
Voltage Regulation± 1% for DC I/p variation & o/p load variation
Frequency50Hz ± 0.05Hz
WaveformPWM Sine wave
Harmonic DistortionLess than 3%
Inverter Efficiency> 92%
Power Factor0.8
Overload150% for 60 sec
Crest Factor3:1
Transient Recovery± 4% under full load change and corrected within 60msec
Phase Displacement1200± 10
Audible NoiseLess than 50 dB at 1 Meter

METERING:

Microprocessor based Digital LCD Meter forR,Y,B Output Voltages, Output currents & Frequency, DC Voltage , Battery and Load Percentage

GENERAL:

Dimensions (LxWxH)mm1040x 350 x 910
Operating temperature00C to 500C
HumidityMax 95%, Non-condensing

PROTECTIONS :

Output Overload & Short circuit, Output Under & Overvoltage, DC Under & Overvoltage Input Under & Overvoltage, Single Phasing & Phase unbalance

INDICATIONS & ALARMS

a) Mains onIndication
b) Inverter onIndication
c) DC LowIndication & Alarm
d) faultIndication & Alarm
e) Output OverloadIndication & Alarm

BYPASS FACILITY

Static Bypass Switch(Optional)Bi-directional